Kompensasi Arus Harmonisa, Daya Reaktif dan Arus Urutan Negatif pada Sumber Tegangan Tak Seimbang dengan Implementasi Tapis Daya Aktif Paralel

Riyadi, Slamet and Haroen, Yanuarsyah (2003) Kompensasi Arus Harmonisa, Daya Reaktif dan Arus Urutan Negatif pada Sumber Tegangan Tak Seimbang dengan Implementasi Tapis Daya Aktif Paralel. In: INDUSTRIAL ELECTRONIC SEMINAR 2003, December 16th, 2003, Surabaya. (Unpublished)

[img]
Preview
Text (COVER)
KOMPENSASI ARUS HARMONISA NEW.pdf

Download (15kB) | Preview
[img] Text (ISI)
KOMPENSASI ARUS HARMONISA ISI.pdf
Restricted to Registered users only

Download (58kB)

Abstract

A control strategy for shunt active power filter to improve power quality with unbalanced ac source is proposed in this paper. By using abcab transformation, distorted load currents and positive sequence input voltages are transformed into two axes coordinates to obtain instantaneous real power. Based on dc component of instantaneous real power, active source currents references will be calculated. These currents are sinusoidal whose each phases shifted 120o. Compensating currents are determined by subtracting the source references from load currents. Compensation of harmonics, reactive power and unbalance are well done by active power filter with the proposed strategy . Simulation is given to complete analysis.

Item Type: Conference or Workshop Item (Paper)
Subjects: 600 Technology (Applied sciences) > 620 Engineering > 621 Electrical engineering
Divisions: Faculty of Engineering > Department of Electrical Engineering
Depositing User: Mrs. Rini Yastuti
Date Deposited: 06 Jan 2016 05:03
Last Modified: 10 Mar 2017 03:45
URI: http://repository.unika.ac.id/id/eprint/7194